丹東製藥廠高效過濾器
所屬分類:丹(dān)東高(gāo)效過濾器
- 點擊次數:
- 發布日期:2020/11/26
- 在線詢價
關(guān)於高(gāo)效過濾器的更換周期方麵的問(wèn)題,很多潔淨(jìng)室用(yòng)戶都很關心,畢竟高效(xiào)過濾器決定著潔(jié)淨室(shì)的潔(jié)淨度(dù)能否達到標準,就在前方我(wǒ)們也整理過相關方麵的問(wèn)題(tí):高效過濾器的更換標準
In the pharmaceutical industry, HEPA filters are used as terminal filters for the processing or filtration of air in production spaces. They are mandatory in sterile production, although they are sometimes also used in the manufacture of solid or semisolid dosage forms. Amongst the HEPA or high-efficiency particulate air filters are Filter Classes H13 to H14 (DIN 1822), the latter with a retention rate of 99.995%. But how often do they need to be changed?
在製藥行業,高效過濾器(HEPA)用於生產空間空(kōng)氣的處理和過濾的終端過(guò)濾器。無菌生產要求強製使用高效過濾器,而固體和半固(gù)體劑型的生(shēng)產有時也會使用。H13至H14(DIN1822)是高效(xiào)過濾器的兩(liǎng)種,後者截留率(lǜ)為99.995%。但多久(jiǔ)必須(xū)更換一次呢?
One can frequently find internal company guidelines according to which the filters should be changed annually, regardless of monitoring results. Is that sensible? An exact number, meaning the maximum duration of use for HEPA filters in months, cannot be found in the relevant GMP guidelines. According to GMP, the filter has to be free of leaks. This is verified by qualification and regularly performed leak tests as per ISO 14644-3, which are mandatory for sterile facilities. According to the technical 參考:(www.ljinghua.com)interpretation of the Annex 1 (PIC/S PI 032-2), leak tests are to be performed every six months in A/B zones and every twelve months in C/D zones. The FDA Aseptic Guide demands a regular inspection. The requirements of Annex 1 can be applied here as well. Leaks may be repaired; those repaired areas may only take up 0.5% of the filter surface per filter.
製藥廠高效過濾器一般多久(jiǔ)更換?
我(wǒ)們經常看到在公司內部文件(jiàn)中,要求每年更換過濾器,而不管檢測結(jié)果如何。這是否合(hé)理?在相關的GMP指南中並沒有高效過濾器可(kě)以使用期限的具體數值。根據GMP的要求(qiú),過濾器不(bú)得有泄漏,這需要通過確認和定期執行ISO14644-3中的(de)泄漏測試,無菌車間來說這是必須的。根據附錄(lù)1(PIC/S PI032-2)的技術詮釋,A/B級每6個(gè)月進行泄(xiè)漏測試,C/D級則為12個月。FDA無菌指南(nán)要求進行定期(qī)檢查。附錄1的要求(qiú)在這裏也適(shì)用。泄漏是可以修補的,但修(xiū)補的麵積不能超過(guò)單個過濾器麵積的0.5%。)
However, not only the integrity of the HEPA filter is relevant. The load of the filter (layer) and thus the pressure drop at the filter is also important. If the pressure drop at the filter rises, the energy demand of the ventilation system increases to maintain the necessary air change rates. This pressure drop at the filter can increase to the performance limits of the ventilation system. To protect the HEPA filters, preliminary filters are used - usually fine particulate air filters like F7 und F9 filters (EN779). Those have to be replaced regularly and protect the HEPA filters from clogging.
當(dāng)然(rán),廣州靈潔淨化高效過濾器(qì)並不隻有完整性一件事情。過濾器(層)的負載(zǎi)以及上下遊(yóu)壓差也(yě)很重要。如果過濾器上下遊壓(yā)差升(shēng)高,則送排風係統的(de)能量(liàng)需求會增(zēng)加,這樣才能維持必(bì)須(xū)的換氣次數。這樣(yàng)的過濾器上下遊壓差可能(néng)會增加通風係統的性能限製。為了保護高效過濾器,就要使用前端過濾器---通常是像F7和F9過(guò)濾器(EN779)這樣的精細過濾器。這些過(guò)濾器必須定期更換(huàn)以保(bǎo)護高效過濾器避免堵塞(sāi)
From a practical viewpoint, one could say that the maximum duration of use depends directly on the pressure drop. Changing the filters only makes sense if the pressure drop gets too high for the performance of the ventilation system or if the cost of energy demand lies above the cost of a filter change. The filters do have to pass the leak tests (see above), of course. In practice, several companies do not use a filter for more than eight years. As mentioned before, though, this is not a legally binding value, but merely based on experience.
從(cóng)實踐角度來看,草莓秋葵菠萝蜜黄瓜榴莲视频可以說(shuō)最長使用期限直接取決於上下(xià)遊壓差。隻有在上下遊壓差達到一定數值影響到通風係統(tǒng)的性能,或者是(shì)能量需求超過過濾器更換成本時,過濾器更換才有意義。但是,過(guò)濾器必須(xū)能(néng)通過泄漏測試(如上所述)。事實上,很多(duō)公司並不會使用一(yī)個過濾器超過8年。正如前述,並(bìng)沒有法規規定這樣的值,這都隻是根據經驗得來的。
靈潔高效過濾器更換問(wèn)題
谘詢內容:老師您好,小容量注射劑車間空調係統的高效過濾(lǜ)器必須定期更換嗎?如不定期更換,隻(zhī)在空調(diào)驗證時更換風量(liàng)不合格房間高效和撿漏不合格(gé)高效可以(yǐ)嗎?
CFDA審核查驗中心回複:你好,更換高(gāo)效過濾器根據空調驗證(zhèng)參考:時風量和撿漏(lòu)是必須的,但同時也應製定出具體高效過濾器(qì)最長使(shǐ)用周期(qī),故還是應該(gāi)有定期的概念。同時必須(xū)定期(qī)進行過(guò)濾器完整性測試。
製藥廠高效(xiào)過濾器一般多久更換?
潔淨區A級(jí)高效過濾器檢漏(lòu)
谘詢內容(róng):潔淨區A級高效過濾器(qì)檢漏是否可以使用 塵埃粒子計數器 掃描檢(jiǎn)漏,如果可以,那麽判斷無泄漏的標準是多少。
CFDA審核查驗中心回複:靈潔高效過濾器檢漏一般在非關鍵區域可以使用塵埃粒子計數器,但A級潔(jié)淨區高效過濾(lǜ)器不推薦使用塵埃粒子計數器掃描檢(jiǎn)漏