關於高(gāo)效過濾器的(de)更換周期方麵的問(wèn)題,很(hěn)多潔(jié)淨室用戶都很關心,畢竟高效過濾器決定著潔淨室的潔淨度能否達到標準,就(jiù)在前方草莓秋葵菠萝蜜黄瓜榴莲视频也整理(lǐ)過相關方(fāng)麵的(de)問題:高效過濾器的更換標準
In the pharmaceutical industry, HEPA filters are used as terminal filters for the processing or filtration of air in production spaces. They are mandatory in sterile production, although they are sometimes also used in the manufacture of solid or semisolid dosage forms. Amongst the HEPA or high-efficiency particulate air filters are Filter Classes H13 to H14 (DIN 1822), the latter with a retention rate of 99.995%. But how often do they need to be changed?
在製藥行業,高效過濾器(qì)(HEPA)用於生產(chǎn)空間空氣的處理和過濾的終端過濾器。無菌生產要求強製使用(yòng)高效(xiào)過濾器,而固體和半(bàn)固體劑型(xíng)的(de)生產有時也會使用。H13至H14(DIN1822)是高效過濾器的兩種(zhǒng),後(hòu)者截(jié)留率為99.995%。但多久必須更換一次呢?
One can frequently find internal company guidelines according to which the filters should be changed annually, regardless of monitoring results. Is that sensible? An exact number, meaning the maximum duration of use for HEPA filters in months, cannot be found in the relevant GMP guidelines. According to GMP, the filter has to be free of leaks. This is verified by qualification and regularly performed leak tests as per ISO 14644-3, which are mandatory for sterile facilities. According to the technical 參考:(www.ljinghua.com)interpretation of the Annex 1 (PIC/S PI 032-2), leak tests are to be performed every six months in A/B zones and every twelve months in C/D zones. The FDA Aseptic Guide demands a regular inspection. The requirements of Annex 1 can be applied here as well. Leaks may be repaired; those repaired areas may only take up 0.5% of the filter surface per filter.
製藥廠高效(xiào)過濾器一般多久更換?
草莓秋葵菠萝蜜黄瓜榴莲视频經常看到在公司內部文(wén)件中,要求每年更換過濾器,而不管檢測結(jié)果如何(hé)。這是否合理?在相(xiàng)關的GMP指南中並沒有高效過(guò)濾(lǜ)器可以使用期限的具體數(shù)值。根據GMP的要求,過濾器(qì)不得有泄漏,這(zhè)需要通過確認(rèn)和定期執行(háng)ISO14644-3中的泄漏測(cè)試,無菌車間來(lái)說這是必須(xū)的。根據附錄1(PIC/S PI032-2)的技術詮(quán)釋,A/B級每6個月進行泄漏測試(shì),C/D級則為12個月。FDA無(wú)菌指南要(yào)求進行定(dìng)期檢查。附錄1的要求(qiú)在這(zhè)裏也適用。泄漏是可以修補的(de),但修補的麵積不能超過單個過濾器麵(miàn)積的0.5%。)
However, not only the integrity of the HEPA filter is relevant. The load of the filter (layer) and thus the pressure drop at the filter is also important. If the pressure drop at the filter rises, the energy demand of the ventilation system increases to maintain the necessary air change rates. This pressure drop at the filter can increase to the performance limits of the ventilation system. To protect the HEPA filters, preliminary filters are used - usually fine particulate air filters like F7 und F9 filters (EN779). Those have to be replaced regularly and protect the HEPA filters from clogging.
當然,廣州靈潔淨化高效過濾器並不隻有完(wán)整(zhěng)性一件事(shì)情。過濾器(層)的負載以及(jí)上下遊壓差也很重要。如果過濾器上下遊壓差升高,則送排風係(xì)統的能量需求會增加,這樣才(cái)能維持必須(xū)的換氣次數。這樣(yàng)的過濾器(qì)上下遊壓差可能會增加通風係(xì)統的性能限製。為了保護高效過濾(lǜ)器,就要(yào)使用前端過濾器---通(tōng)常是像F7和F9過濾器(EN779)這樣的精細過濾器。這些過濾器必(bì)須定期更換以保護高效過濾器避免堵塞
From a practical viewpoint, one could say that the maximum duration of use depends directly on the pressure drop. Changing the filters only makes sense if the pressure drop gets too high for the performance of the ventilation system or if the cost of energy demand lies above the cost of a filter change. The filters do have to pass the leak tests (see above), of course. In practice, several companies do not use a filter for more than eight years. As mentioned before, though, this is not a legally binding value, but merely based on experience.
從實踐角度來看,草莓秋葵菠萝蜜黄瓜榴莲视频可以說最長(zhǎng)使用期限直接取(qǔ)決(jué)於上下遊壓差。隻有在上下遊壓差達到一定數值影響到通風係統的性能,或者是能量需求超過過濾器更換成本時,過濾器更換才有意義。但是,過濾器必須能(néng)通過泄漏測試(如上所述)。事實上,很多公司並不會使(shǐ)用一個過濾器超過8年。正如前述,並沒有法規規定這(zhè)樣的值,這都隻是根據經驗得來的。
靈潔高效過濾器更換問題
谘詢內容:老師您好,小容量(liàng)注射劑車間(jiān)空調係統的高效過濾器必須定期更換嗎?如不定期更換,隻在空調驗證時更換風量不合格房間高效和撿漏不合格高效可以嗎?
CFDA審核查驗中(zhōng)心回複:你好,更換高效過濾器根據空調驗證參考:時風量和撿漏是必須的,但同時也應製定出具(jù)體高效過濾器(qì)最長使用(yòng)周期,故還是應該有定(dìng)期的概念。同時必(bì)須定期進行過濾器完(wán)整性測試。
製藥廠高效過濾器一般多久更換?
潔(jié)淨區A級高效過濾器檢漏
谘詢內容:潔淨區A級高效(xiào)過濾器檢漏是否可以使用 塵埃粒子計(jì)數器 掃描檢漏,如果可(kě)以,那麽判斷無泄漏的標(biāo)準是多少。
CFDA審核查驗中心回複:靈潔高效過濾器檢漏一般在非關鍵區域可以(yǐ)使用塵埃粒子計(jì)數器,但A級潔淨區(qū)高效過濾器不推(tuī)薦使用塵埃粒子計數器掃(sǎo)描檢漏