遂寧製藥(yào)廠高效過濾器
所屬分類:遂寧高效過濾器(qì)
- 點擊次數(shù):
- 發布日期:2020/11/26
- 在線詢價
關於高效過濾器的更換周期方麵的問題,很多潔淨室用(yòng)戶都很(hěn)關心(xīn),畢竟高效過濾器決定著潔(jié)淨室的潔淨度能否達到標準,就在前(qián)方草莓秋葵菠萝蜜黄瓜榴莲视频也整理過相關(guān)方麵的問題:高效過(guò)濾(lǜ)器的更換標準(zhǔn)
In the pharmaceutical industry, HEPA filters are used as terminal filters for the processing or filtration of air in production spaces. They are mandatory in sterile production, although they are sometimes also used in the manufacture of solid or semisolid dosage forms. Amongst the HEPA or high-efficiency particulate air filters are Filter Classes H13 to H14 (DIN 1822), the latter with a retention rate of 99.995%. But how often do they need to be changed?
在製藥行業(yè),高效過濾器(HEPA)用於生產空間空氣的處理和過濾的終端(duān)過濾器。無菌生產要求強製使用高效過(guò)濾器,而固體(tǐ)和半固體劑型的生產有時也會使用(yòng)。H13至(zhì)H14(DIN1822)是高效過濾器的兩種,後者(zhě)截留(liú)率為99.995%。但多久必須更換一次呢?
One can frequently find internal company guidelines according to which the filters should be changed annually, regardless of monitoring results. Is that sensible? An exact number, meaning the maximum duration of use for HEPA filters in months, cannot be found in the relevant GMP guidelines. According to GMP, the filter has to be free of leaks. This is verified by qualification and regularly performed leak tests as per ISO 14644-3, which are mandatory for sterile facilities. According to the technical 參考:(www.ljinghua.com)interpretation of the Annex 1 (PIC/S PI 032-2), leak tests are to be performed every six months in A/B zones and every twelve months in C/D zones. The FDA Aseptic Guide demands a regular inspection. The requirements of Annex 1 can be applied here as well. Leaks may be repaired; those repaired areas may only take up 0.5% of the filter surface per filter.
製藥廠高效過濾器一般多久更換?
草莓秋葵菠萝蜜黄瓜榴莲视频(men)經常(cháng)看(kàn)到在公司內部文件中,要求每年更(gèng)換過濾器,而不管檢測結果如何。這是(shì)否合理?在相關的(de)GMP指南中並沒(méi)有(yǒu)高效過濾(lǜ)器可以使用(yòng)期限的具體數值。根據GMP的要求,過濾器不(bú)得有泄漏,這需(xū)要(yào)通過確認和定期執行ISO14644-3中的泄(xiè)漏測試,無菌車間來說這是必須的。根(gēn)據(jù)附錄1(PIC/S PI032-2)的技術詮釋,A/B級每6個月進行泄漏測試,C/D級則為12個月。FDA無菌指(zhǐ)南要求進行定期檢查。附錄1的要(yào)求在這裏也適用。泄漏是可以修補的,但修補的麵積不能超過單個過濾器麵積的0.5%。)
However, not only the integrity of the HEPA filter is relevant. The load of the filter (layer) and thus the pressure drop at the filter is also important. If the pressure drop at the filter rises, the energy demand of the ventilation system increases to maintain the necessary air change rates. This pressure drop at the filter can increase to the performance limits of the ventilation system. To protect the HEPA filters, preliminary filters are used - usually fine particulate air filters like F7 und F9 filters (EN779). Those have to be replaced regularly and protect the HEPA filters from clogging.
當然(rán),廣州靈潔淨化高效過濾器並不隻有完整(zhěng)性一件事情。過(guò)濾器(層)的負載以及上下遊壓差也很重要(yào)。如果過濾器上下遊壓差升高,則送排風係統的能量需求會增(zēng)加,這樣才能維持必須的換氣次數。這樣的過濾器上下遊壓差可能會增加通風(fēng)係統(tǒng)的性能限製。為了保護高效過濾器,就(jiù)要(yào)使用前(qián)端(duān)過濾器(qì)---通常是像F7和F9過濾器(EN779)這樣的精細過濾器。這些過濾器(qì)必須定期更換以保護高(gāo)效過濾器避(bì)免(miǎn)堵塞
From a practical viewpoint, one could say that the maximum duration of use depends directly on the pressure drop. Changing the filters only makes sense if the pressure drop gets too high for the performance of the ventilation system or if the cost of energy demand lies above the cost of a filter change. The filters do have to pass the leak tests (see above), of course. In practice, several companies do not use a filter for more than eight years. As mentioned before, though, this is not a legally binding value, but merely based on experience.
從實踐角度來看,草莓秋葵菠萝蜜黄瓜榴莲视频可(kě)以說最長使用期限直接取決於上下遊壓差。隻有在上(shàng)下遊壓差達到一定數值影響到通風係統(tǒng)的性能,或者是能量需求超過過濾器更換成本時,過濾(lǜ)器更(gèng)換才有意(yì)義。但是(shì),過濾器必須能通過泄漏測試(如上(shàng)所述(shù))。事實上,很多公司並不會(huì)使用一個過濾(lǜ)器超過8年。正(zhèng)如前述,並沒有法規規定這樣的值,這都(dōu)隻是(shì)根據經驗得來的(de)。
靈潔高效過濾器更換問題
谘詢內容:老師您好,小容量注射劑車間空調係統的高效過濾器必須定期更換嗎?如不定期更換,隻在空(kōng)調驗證時(shí)更換風量不合格房間高效和撿漏不合格高效(xiào)可以嗎(ma)?
CFDA審核查驗中(zhōng)心回複:你(nǐ)好,更換高效過濾器根據空調驗證參考:時風量和撿漏是必須的,但同時也應製定出具體高效過濾器最長使用(yòng)周期,故(gù)還是應該有定期的概念。同時必須定期進行過濾(lǜ)器(qì)完整性測(cè)試。
製藥廠高效過濾(lǜ)器一般(bān)多(duō)久更(gèng)換?
潔淨區A級高效過濾器檢漏
谘詢(xún)內容:潔淨區A級高效過濾器檢(jiǎn)漏是否可以使用 塵(chén)埃粒(lì)子(zǐ)計數器 掃描檢漏,如果可以,那麽判斷無泄漏的標準是多少。
CFDA審核查驗中心回複:靈潔高(gāo)效過濾器檢漏一(yī)般在非關鍵區域可以使用塵埃粒子計數器,但A級潔淨區高效過濾器不推薦使用塵埃粒子計數器掃描檢漏